C-8
F650 Digital Bay Controller
GEK-106310AB
C.3 IMPLEMENTATION TABLE
APPENDIX C
C
b) IMPLEMENTATION TABLE (SHEET 2 OUT OF 3)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01
(for change-event objects, qualifiers 17 or 28 are always responded).
Note 3: Cold restarts are implemented the same as warm restarts – The F650 is not restarted, but the DNP process is restarted.
OBJECT
REQUEST
RESPONSE
Object
No.
Variation
No.
Description
Function Codes
(dec)
Qualifier Codes (hex) Function Codes Qualifier Codes
(hex)
21
0
Frozen Counter - All Variations
1
(read)
06
(no range, or all)
22
0
Counter Change Event - All
Variations
1
(read)
06
(no range, or all)
07,08
(limited qty)
30
0
Analog Input - All Variations
1
(read)
22
(assign class)
06
(no range, or all)
00,01
(start-stop)
07,08
(limited qty)
17,28
(index)
30
1
32-Bit Analog Input
See Note 1
1
(read)
22
(assign class)
000,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
2
16-Bit Analog Input
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
3
32-Bit Analog Input without Flag
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
4
16-Bit Analog Input without Flag
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
32
0
Analog Change Event - All Variations 1
(read)
06
(no range, or all)
07,08
(limited qty)
32
1
32-Bit Analog Change Event without
Time
See Note 1
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17, 28
(index)
32
2
16-Bit Analog Change Event without
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17, 28
(index)
32
3
32-Bit Analog Change Event with
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17,28
(index)
32
4
16-Bit Analog Change Event with
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17,28
(index)
34
0
Analog Input Reporting Deadband
1
(read)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
34
1
16-Bit Analog Input Reporting
Deadband
See Note 1
1
(read)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00,01
(start-
stop)
17,28
(index)
See Note 2
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...