GEK-106310AB
F650 Digital Bay Controller
11-3
11 APPLICATION EXAMPLES
11.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
11
11.1.3 PROCEDURE TO SET THE PROTECTION FUNCTION
Once the relay has been connected set protection functions and outputs according to the following steps:
Open EnerVista 650 SETUP program and under:
SETPOINT
SYSTEM SETUP
GENERAL SETTINGS
Under
SETPOINT
PROTECTION ELEMENTS
PHASE CURRENT
PHASE TOC HIGH
PHASE TOC HIGH
1
Under
SETPOINT
CONTROL ELEMENTS
INPUTS/OUTPUTS
BOARD F
Under
SETPOINT
RELAY CONFIGURATION
OUTPUTS
NAME
VALUE
Phase CT Ratio
1.0 (default)
Ground CT Ratio
1.0 (default)
Stv Ground CT Ratio
1.0 (default)
Phase VT Ratio
1.0 (default)
Phase VT Connection
Wye
Nominal Voltage
100.0 (default)
Nominal Frequency
50
Phase Rotation
ABC
Frequency Reference
VI (default)
Auxiliary Voltage
VX (default)
NAME
VALUE
Function
Enabled
Input
Phasor DFT
Pickup Level
5.0 A
Curve
IEC Curve A
TD Multiplier
0.1
Reset
Instantaneous
Voltage Restraint
Disabled
NAME
VALUE
Output Logic_00_00
Positive
Output Type_00_00
Latch
SELECT
NAME
SOURCE
OR
Contact Output Operate 00 (Board F)
C Output Oper_00_00
PRESS FOR LOGIC
Phase TOC A Op
Phase TOC B Op
Phase TOC C Op
Contact Output Reset 00 (Board F)
C Output Reset_00_00
Operation bit 000
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...