GEK-106310AB
F650 Digital Bay Controller
5-3
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2PRODUCT SETUP
5.2.1 COMMUNICATION SETTINGS
5.2.1.1 SERIAL PORTS
Baud rate and parity for COM1 and COM2 serial communication ports.
Table 5–2: SERIAL PORTS SETTINGS
5.2.1.2 NETWORK (ETHERNET)
Ethernet communication parameters for COM3. Two different Ethernet addresses can be used, but the first IP always has
to be set as the second IP Address is an Alias. The ModBus Slave address used by Ethernet ports is the one set for COM2.
Table 5–3: NETWORK SETTINGS
5.2.1.3 MODBUS PROTOCOL
ModBus Slave Addresses for serial and Ethernet communication and the ModBus port number used for ModBus TCP/IP.
For more detailed information go to appendix B in this manual.
Table 5–4: MODBUS PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >SERIAL PORTS
Name
Default Value
Step
Range
COM1 Baud Rate
19200
N/A
[300 : 115200]
COM2 Baud Rate
19200
N/A
[300: 115200]
COM1Parity
NONE
N/A
[NONE:ODD:EVEN]
COM2Parity
NONE
N/A
[NONE:ODD:EVEN]
PRODUCT SETUP > COMMUNICATION SETTINGS >NETWORK (ETHERNET) NETWORK
(ETHERNET)1 > NETWORK (ETHERNET)2
Name
Default Value
Step
Range
IP Address Oct1
0
N/A
[0: 255]
IP Address Oct2
0
N/A
[0: 255]
IP Address Oct3
0
N/A
[0: 255]
IP Address Oct4
0
N/A
[0: 255]
Netmask Oct1
0
N/A
[0: 255]
Netmask Oct2
0
N/A
[0: 255]
Netmask Oct3
0
N/A
[0: 255]
Netmask Oct4
0
N/A
[0: 255]
Gateway IP Oct1
0
N/A
[0: 255]
Gateway IP Oct2
0
N/A
[0: 255]
Gateway IP Oct3
0
N/A
[0: 255]
Gateway IP Oct4
0
N/A
[0: 255]
PRODUCT SETUP > COMMUNICATION SETTINGS >MODBUS PROTOCOL
Name
Default Value
Step
Range
ModBus Address COM1 254
1
[1 : 255]
ModBus Address COM2 254
1
[1 : 255]
ModBus Port Number
502
1
[0 : 65535]
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...