7-82
F650 Digital Bay Controller
GEK-106310AB
7.3 IEC 61850 CONFIGURATOR
7 IEC 61850 PROTOCOL
7
The mapping of incomming DNA and UserSt bits to Remote Inputs is done in case of Fixed GOOSE in menu in the "IEC
61850 Configurator" tool.
It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between F650
relay and UR series IEDs.
Configurable GOOSE is recommended for implementations that require GOOSE data transfer between F650 relays and
devices from other manufacturers.
USING "IEC 61850 CONFIGURATOR" FOR GOOSE SETUP
The F650 relay allows a maximum of four transmission GOOSE applications and a maximum of 16 reception GOOSE
applications. Maximum one of the transmission GOOSEs can be Fixed GOOSE and maximum one of the reception
GOOSEs can be Fixed GOOSE. Fixed GOOSE can be used at the same time as configurable GOOSE.
In F650 Data Sets for configurable GOOSE, both for reception and transmission, can have a maximum of 64 elements.
The elements of Data Sets for transmission GOOSEs can only be leaf elements (Data Attributes), and cannot be complex
structures (Data Objects).
The elements of Data Sets for reception GOOSEs can be of any types supported in IEC 61850 standard and can be both
leaf elements (Data Attributes) and compelx structures (Data Objects). However F650 relay can map to its internal
variables incomming data of type Boolean, Float, Integer and any of the bits from Bitstring data type.
Configuration of the transmission part of GOOSE
GOOSE Transmission tab contains four different panels:
•
GOOSE TX Main:Lists all GOOSE control blocks present in the device
•
DataSet Sources:Enables the user to browse through complete data model, select data attributes and drag them to the
DataSet (DataSet panel on the right)
•
GOOSE TX Properties:Shows parameters of selected GOOSE control block and VLAN settings
•
DataSet:Shows the name of the GOOSE DataSet and list all of its members
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...