2-28
F650 Digital Bay Controller
GEK-106310AB
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 y 115200 bauds
Default Baud Rate
19200
Protocols available:
ModBus
®
RTU / DNP 3.0/IEC103
Typical distance:
1200 m for cooper cable, 1000 m for glass fiber and 50 m for plastic
fiber
Isolation:
2 kV
CAN PORT:
Rear port:
CAN port in models C, M, X, Y, Z for asynchronous rear ports
Type:
Multimode glass F.O. port with ST connectors
Fiber Wave length:
820 nm
Fiber type:
multimode 62.5/125
μ
m or 50/125
μ
m
Maximum recommended length
300m
for cooper cable and glass fiber
Isolation:
2 kV
ETHERNET PORT:
Rear port:
COM3
Type (depending on model):
Model B:
10/100BaseTX self-negotiable
Model C:
10/100 100Base FX
Model D:
10/100 redundant 100BaseFX (Physical media redundancy)
Model E:
Redundant 10/100BaseTX self-negotiable ports
10/100BaseTX
RJ45 connector
100BaseFX
ST connectors
Wave length:
1300 nm
Fiber type:
multimode 62.5/125
μ
m or 50/125
μ
m
Protocols available:
ModBus® TCP/IP
DNP over TCP/IP and UDP/IP
IEC 61850
Http, ftp, tftp (allow the use of a standard Internet browser)
Typical distance:
1000 m for glass fiber and 300 m for RJ45 cable
Response time to ModBus commands:
10 ms Typical
Isolation:
2 kV
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED’s for transmission and reception are included
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...