5-110
F650 Digital Bay Controller
GEK-106310AB
5.5 CONTROL ELEMENTS
5 SETTINGS
5
The signals related to the locked rotor pickups and operations for the three locked rotor elements can be viewed at
Actual
> Status > Control Elements > Locked Rotor
and they are as follows:
Table 5–88: LOCKED ROTOR STATUS
The block signals for the locked rotor element can be configured at:
Setpoint > Relay Configuration > Protection
Elements
Table 5–89: LOCKED ROTOR BLOCKS
Note:
The element works with primary values.
The element will pickup if at least one of the three phase currents is above the adjusted level. The operation value will be
the higher of the three.
The reset level is 97% to 98% of the pickup level.
5.5.10 PULSE COUNTERS
The F650 includes eight pulse counters, each pulse counter stores the activation number of the input set to that pulse
counter. This value can be multiplied for a factor selectable by setting.
The inputs used in this pulse counter function can be selected from all the available in the F650 device. Take into account
that the input/output settings are both set for the generic input as well as for the pulse counter input, e.g. Debounce time.
The settings for this function can be found at
Setpoint > Control Elements > Pulse Counters
Table 5–90: PULSE COUNTERS SETTINGS
Pulse Counters settings are:
CntPulses Enabled:
Enable/disable each pulse counter.
CntPulses Name:
Each pulse counter can have a configurable user name.
LOCKED ROTOR STATUS
LOCKED ROTOR1 PKP
LOCKED ROTOR1 OP
LOCKED ROTOR2 PKP
LOCKED ROTOR2 OP
LOCKED ROTOR3 PKP
LOCKED ROTOR3 OP
LOCKED ROTOR BLOCKS
LOCKED ROTOR1 BLK
LOCKED ROTOR2 BLK
LOCKED ROTOR3 BLK
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP RANGE
Pulse counter enabling setting
CntPulses Enabled X
DISABLED
N/A
[DISABLED – ENABLED]
Name of the pulse counter
CntPulses Name X
Pulse Counter X
N/A
N/A
Multiplier factor for the pulse counter
CntPulses Factor X
1.000
0.001
[0.000 : 65000.000]
Overflow value for the pulse counter
CntPulses Overflow X
65535
1
[0 : 1000000]
Board selection for the pulse counter
CntPulses Board Origin X
F
N/A
[F,G,H,I]
Input index inside the selected board
CntPulses Input Origin X
1
1
[1 : 32]
Note: X is the pulse counter index, up to 8.
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...