7-32
F650 Digital Bay Controller
GEK-106310AB
7.2 IEC 61850 PROFILE FOR F650
7 IEC 61850 PROTOCOL
7
2.2.5 PTUV (Undervoltage)
2.2.5.1 phsPTUV
This logical node class is used for phase undervoltage and has 3 instances inside the device.
Notes:
TmVCrv object uses Enum type setCharact_2 (See the Enum types implementation section).
ACT includes origin attribute in ST, this is implemented according to Tissue 68.
PTUV class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
PTUV
Undervoltage
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Status Information
Str
ACD
Start
M
TUV PKP
Op
ACT
Operate
M
TUV OP
Blk
ACT
Block
E
TUV BLK
StrPhGn
ACD
Start
E
TUV Phase-Gnd PKP
OpPhGn
ACT
Operate
E
TUV Phase-Gnd OP
StrPhPh
ACD
Start
E
TUV Phase-Phase PKP
OpPhPh
ACT
Operate
E
TUV Phase-Phase OP
Settings
TmVCrv
CURVE_2
Operating curve type
O
Curve ( definitive, inverse )
StrVal
ASG
Start value
O
Pickup Level (3 – 300)
TmMult
ASG
Time dial multiplier
O
Delay (0 – 900)
DeaLinVal
ASG
Minimum Voltage
E
Minimum Voltage (0 – 300)
PhLogic
ING
Logic
E
Logic (Any, Two, All phases)
InMod
ING
Mode
E
Phase-Phase, Phase-Ground
BkrMon
SPG
Supervised by 52
E
Enable, Disable
PTUVEna
SPG
Function TUV enable
E
Function
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...