GEK-106310AB
F650 Digital Bay Controller
7-45
7 IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR F650
7
Note:
actVal in BCR is imlemented as INT32.
In the F650 there are up to 16 configurable switchgears. Currently four XSWI and four CSWI are implemented and mapped
to first nine switchgears in F650. XSWI and CSWI Logical Nodes can be seen as paired objects in F650 as one pair of
XSWI and CSWI map to the same swithcgear. XSWI1 and CSWI1 map to Switchgear1, XSWI2 and CSWI2 map to
Switchgear2, etc. The difference between XSWI and CSWI in F650 is that control commands cannot be sent directly via
XSWI LN. Control commands have to be sent via CSWI LN.
In F650 relay the Circuit Breaker (XCBR1 Logical Node) by default is mapped to first switchgear (exactly like XSWI1 and
CSWI1 LNs). However it is possible to map the Circuit Breaker to any of the 16 switchgears of F650 relay. It can be done by
modification of the following setting:
Setpoint->System Setup-> Breaker Settings->Number of Switchgear
.
In XCBR LN for "Pos" controllable attribute all possible control models are applicable:
•
"direct-control-with-normal-security"
•
"SBO-control-with-normal-security"
•
"direct-control-with-enhanced-security"
•
"SBO-control-with-enhanced-security"
The sboTimeout attribute for Pos is configurable in a range from 500 ms to 60 seconds.
The sboClass attribute for Pos can only have value "0" (operate-once).
2.7.2 XSWI (Circuit switch)
In the F650 there are up to 16 configurable switchgears. Currently four XSWI and four CSWI are implemented and mapped
to first nine switchgears in F650. XSWI and CSWI Logical Nodes can be seen as paired objects in F650 as one pair of
XSWI and CSWI map to the same swithcgear. XSWI1 and CSWI1 map to Switchgear1, XSWI2 and CSWI2 map to
Switchgear2, etc. The difference between XSWI and CSWI in F650 is that control commands cannot be sent directly via
XSWI LN. Control commands have to be sent via CSWI LN.
"Pos" attribute is not controllable in XSWI it has ctlModel = Status-only. In order to control the switch mapped to given XSWI
the corresponding CSWI LN should be used.
XSWI class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
XSWI
Circuit switch
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Loc
SPS
Local operation
M
Local / Remote
EEHealth
INS
External equipment health
O
OpCnt
INS
Operation counter
M
Breaker openings
Controls
Pos
geDPC
Switch position
M
Status-only
BlkOpn
SPC
Block opening
M
Status-only
BlkCls
SPC
Block closing
M
Status-only
Status information
SwTyp
INS
Switch Type
M
Fixed value = 2 (Disconnector)
SwOpCap
INS
Switch operating capability
M
Fixed value = 5
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...