9.2 COMMUNICATION PARAMETERS
Before proceeding with the upgrade process, it is mandatory to check the following:
1.
Since F650 Setup Program acts as a TFTP sever, any other TFTP server installed in the PC must be disabled
.
C
heck if any other TFTP server is installed in the PC and/or if any other device is using Port 69 that it might be
installed by default during the PC startup
. To disable it please proceed as follows in the PC:
•
At
STARTUP>MY PC>Right Mouse key>MANAGE>SERVICES & APPLICATIONS> SERVICES
•
Select the operative
TFTP server
•
Right Mouse key>MANUAL or STOP
•
Reboot PC
(if
MANUAL
)
2.
Ethernet Connection/Type - Both boot code and firmware upgrade processes require Ethernet communications. It is
strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet
cable, instead a direct connection through a hub or switch. In no one case upgrading will be done using a Local Area
Network (LAN).
Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade.
3.
Relay IP Address - It must be assigned a IP address to the relay in the Ethernet parameters via HMI at
PRODUCT
SETUP>COMMUNICATION>ETHERNET>ETHERNET1
menu or via Enervista 650 Setup at
SETPOINT>PRODUCT
SETUP>COMMUNICATION SETTINGS>NETWORK (Ethernet) 1
as shown in the Table 9–1:
Table 9–1: ETHERNET PARAMETERS
4.
PC IP Address - In the case the relay has been boot code previously upgraded (section 9.2), the IP address and other
parameters already assigned in the process will be:
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET) 1
NAME
VALUE
UNITS
RANGE
IP Address Oct1
192
[0 : 255]
IP Address Oct2
168
[0 : 255]
IP Address Oct3
37
[0 : 255]
IP Address Oct4
177
[0 : 255]
Netmask Oct1
255
[0 : 255]
Netmask Oct2
255
[0 : 255]
Netmask Oct3
255
[0 : 255]
Netmask Oct4
0
[0 : 255]
Gateway IP Oct1
192
[0 : 255]
Gateway IP Oct2
168
[0 : 255]
Gateway IP Oct3
37
[0 : 255]
Gateway IP Oct4
10
[0 : 255]
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...