7-36
F650 Digital Bay Controller
GEK-106310AB
7.2 IEC 61850 PROFILE FOR F650
7 IEC 61850 PROTOCOL
7
2.3.1.4 hseRDIR
This logical node class is used for sensitive ground directional elements and has 3 instances inside the device.
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
RDIR class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
RDIR
Directional Element
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Status Information
Dir
ACD
Direction
M
Fixed to unknown value
Op
ACT
Operate
E
Sens Gnd Dir OP
Blk
ACT
Block
E
Sens Gnd Dir Block
BlkIn
ACT
Sens Gnd Dir Blk Inp
E
Sens Gnd Dir Blk Inp
Settings
ChrAng
ASG
Characteristic Angle
O
(-90, 90) MTA
BlkValV
ASG
Minimun operating current
O
(0, 300) Pol V Threshold
PolOpMod
ING
Direction
E
(Reverse, Forward)
BlkMod
ING
Block Logical
E
(Prmission, Blocked)
RDIREna
SPG
Function Permission
E
(Enable, Disable)
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...