5-98
F650 Digital Bay Controller
GEK-106310AB
5.5 CONTROL ELEMENTS
5 SETTINGS
5
5.5.5 AUTORECLOSE (79)
5.5.5.1 INTRODUCTION
Note:
The Switchgear element used in the F650 autoreclose element is the one configured in the
Number of Switchgear
setting inside
Breaker settings
, at “
Setpoint > System Setup > Breaker > Breaker settings
”. Configuration of these
Switchgear parameters is performed at
Setpoint > Relay Configuration > Switchgear
using the EnerVista 650 Setup
software.
The F650 autoreclose element allows producing up to four breaker “shots” prior to lockout. Thanks to the great flexibility of
the F650 configurable logic, the conditions to produce the autoreclose initiation and the selection of which protection
elements will be enabled after each shot can be programmed. This flexibility allows implementing protection schemes that
used to require wiring and special functions in conventional equipment. One application is, for instance, to program as
instantaneous the first protection trip and the second one to be time delayed, in order to give time for output fuses to
burning of a feeder branch. This can be as simple as disabling the instantaneous elements after the first shot using the
programmable logic. (see example in section 5.5.5.6)
5.5.5.2 MAIN AUTORECLOSE SETTINGS
Setpoint > Control Elements > Autoreclose
Table 5–80: 79 ELEMENT SETTINGS
Autoreclose settings description:
Function:
This setting allows enabling or disabling the autoreclose operation. If this setting is adjusted as
DISABLED, the recloser will be out of service.
Max Number Shots:
This setting specifies the number of autoreclose shots allowed in the element. If this number is
exceeded, the autoreclose goes to LOCKOUT status, and the fault is considered to be permanent.
Dead Time 1 ... 4:
These times correspond to the first, second, third and fourth breaker reclosings configured in the
element.
Reclaim Time
(also known as
safety time
or
reset lockout delay
)
:
This is the time required to go from LOCKOUT
to READY status once the breaker is closed.
Cond. Permission:
This setting enables the verification of the relay reclose conditions. If this setting is enabled, before
the breaker closing command execution the system will verify the possible reclose conditions. If this
setting is disabled, the closing command will be executed after the reclose time without verifying
these conditions. The reclose conditions input is configured as AR CONDS INPUT at
Setpoint >
Relay Configuration > Protection Elements
Hold Time:
This setting indicates the waiting time for the reclose conditions to be present. This setting is only
operative if the
Cond. Permission
setting is enabled.
Reset Time:
This is the time that the autoreclose takes to return to READY status after a successful reclose. Once
this time has expired, the shot counter will reset and the autoreclose will get to READY.
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Number of shots
Max Number Shots
1
N/A
[1 : 4]
Dead time 1
Dead Time 1
0.00
0.01 s
[0.00 : 900.00]
Dead time 2
Dead Time 2
0.00
0.01 s
[0.00 : 900.00]
Dead time 3
Dead Time 3
0.00
0.01 s
[0.00 : 900.00]
Dead time 4
Dead Time 4
0.00
0.01 s
[0.00 : 900.00]
Reclaim time or reset lockout delay
Reclaim Time
0.00
0.01 s
[0.00 : 900.00]
Reclose conditions permission
Cond. Permission
DISABLED
N/A
[DISABLED – ENABLED]
Hold time
Hold Time
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Time
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...