10.11 INSTANTANEOUS OVERCURRENT (50PH, 50PL, 50N, 50G Y 50SG)
10 COMMISSIONING
10
10.11INSTANTANEOUS OVERCURRENT (50PH, 50PL, 50N, 50G Y 50SG)
Set the relay to trip for the protection element being tested. Configure any of the outputs to be enabled only by the
protection element being tested.
Apply 0.9 times the Pickup current and check that the relay does not trip.
Gradually increase the current value and verify that the relay operates between 1 and 1.1 times the set pickup current. The
relay must trip by instantaneous in a time frame of 10 to 55 ms. All the relay trip contacts must operate, as well as the
contact set as 50.
Remove current and apply it again suddenly to a value of 4 times the pickup current. The relay should trip instantaneously
in a time frame of 10 to 45 ms.
Test one point for each phase and group of the protection element.
Note (*): Only available for Enhanced models
50 ELEMENTS TEST PARAMETERS
Element Settings (50PH, 50PL, 50G y 50SG)
Setting
Value
Units
Function
Enabled
Input
RMS
NA
Pickup Level
3
A
Delay time
0
Seconds
Test Execution
Configure one output for 50 Trip
Apply times I pickup
Element Trip
Tripping times (ms)
0.9 x Pickup
NO
NA
1.1 x Pickup
YES
10-55
4 x Pickup
YES
10-45
Elements
Phase
Group
50PH and 50PL
IA
0
IB
0
IC
0
50G
IG
0
50SG
(*)
ISG
0
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...