GEK-106310AB
F650 Digital Bay Controller
2-27
2 PRODUCT DESCRIPTION
2.4 TECHNICAL SPECIFICATIONS
2
2.4.9 CONTROL POWER SUPPLY
2.4.10 COMMUNICATIONS
LOW RANGE (LO)
Nominal DC Voltage:
24 to 48 V
Min/Max DC Voltage
19.2 / 57.6 V
Note:
Low range is DC only
Voltage Loss hold-up time:
24Vdc 30 ms
48Vdc100ms
HIGH RANGE (HI)
Nominal DC Voltage:
110 to 250 V
Min/Max DC Voltage
88 / 300 V
Nominal AC Voltage:
120 to 230 V
Min/Max AC Voltage
102 / 250 V
Voltage Loss hold-up time 200 ms typical, worst case 100 ms without unit reset
ALL RANGES
Power consumption
Typical =25 VA, Maximum =45 VA
Display backlight auto power-off mode after 15 minutes without touching any key, in order to ensure long life and minimum
consumption.
FRONT PORT:
Front port:
COM2
Type
RS232/USB
Baud Rate
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 y 115200 bauds
Default Baud Rate
19200
Protocols available:
ModBus
®
RTU / DNP 3.0
Typical distance:
3 m
Isolation:
2 kV
ASYNCHRONOUS REAR PORTS:
None or two rear ports (depending on
model):
COM1, COM2 (rear COM2 multiplexed with front port)
Type (depending on model):
Model F
None
Model A
Redundant RS485
Model X
Redundant RS485 + fiber CAN for inputs/outputs module
Model P
Redundant 1mm-plastic F.O.
Model Y
Redundant 1mm-plastic F.O. + fiber CAN for inputs/outputs module
Model G
Redundant multimode glass F.O.
Model Z
Redundant multimode glass F.O. + fiber CAN for inputs/outputs module
Model C
Cable CAN port for I/O module
Model M
Cable CAN port for I/O module (cable) + RS485 (ModBus RTU)
Optic Features for ST connectors
devices:
Wave length: 1300nm
Fiber type: multimode 62.5/125
μ
m or 50/125
μ
m
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...