7-44
F650 Digital Bay Controller
GEK-106310AB
7.2 IEC 61850 PROFILE FOR F650
7 IEC 61850 PROTOCOL
7
2.6.3 MSQI (Sequence and imbalance)
Condition C: At least one of either data shall be used.
2.7 Logical Nodes for switchgear. LN Group: X
2.7.1 XCBR (Circuit Breaker)
MSQI class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
MSQI
Sequence and imbalance
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Measured values
SeqA
SEQ
Positive, Negative and Zero Sequence
Current
C
SeqV
SEQ
Positive, Negative and Zero Sequence
Voltage
C
XCBR class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
XCBR
Circuit breaker
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Number of Switchgear
Loc
SPS
Local operation
M
Local / Remote
OpCnt
INS
Operation counter
M
Breaker openings
Controls
Pos
geDPC
Switch position
M
Breaker open, close, und
BlkOpn
SPC
Block opening
M
Status-only
BlkCls
SPC
Block closing
M
Status-only
Metered Values
SumSwARs
BCR
Sum of Switched Amperes
O
Maximum KI2t value of any of
the phases
Status information
CBOpCap
INS
Circuit breaker operating capability
M
Fixed value = 5
Settings
ThAlSwA
ASG
Threshold Alarm of Switched Amps
E
Maximum KI2t
SumSwATmms
ASG
Sum of sw. Amps integration time
E
KI2t Integ. Time
ExNumTr
ASG
Excessive number of trips
E
Maximum Openings
ExNumTr1hr
ASG
Excessive number of trips in 1 hour
E
Max. Openings 1 hour
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...