5-78
F650 Digital Bay Controller
GEK-106310AB
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
The following table shows the SMIN and angle values that must be used for some typical applications:
Table 5–71: DIRECTIONAL POWER ELEMENT
By adding 90º to the angles shown on figures a, b, c and d, the represented elements would be similar but with
Reactive
Power
instead of Active Power.
Any other angle would provide a mixed Protection Between Active and Reactive power.
A different angle selection for Stage 1 and Stage 2 could provide in a single element, a Reactive and Active power
limitation. For example, using the following values:
Dir Power Angle 1(RCA)
0º
Stage 1 Tap
0
Dir Power Angle 2(RCA)
90º
Stage 2 Tap
0
We would obtain a mixed Protection Between figure (d) and figure (e).
b) SETTINGS
Table 5–72: 32 ELEMENT SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element.
Function:
Enables or disables the directional element.
Blk Time After Close:
In seconds. This settings allow to block the element 32 during the time specified in the
setting after the breaker switches from OPEN to CLOSED.
Dir Power Angle (1-2) (RCA):
This setting specifies the relay characteristic angle (RCA) for the directional power
element. This setting provides ability to respond to the function in any direction defined
(active forward power, active low forward power, etc.)
SMIN (STAGE TAP)
ANGLE (RCA)
ELEMENT
>0
0º
Forward Active Power
<0
0º
Reverse Low Forward Active Power
>0
180º
Reverse Forward Active Power
<0
180º
Low Forward Active Power
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Block from off-line
Blk Time After Close
0.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 1 (RCA1)
Dir Power Angle 1
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 2 (RCA2)
Dir Power Angle 2
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...