5-116
F650 Digital Bay Controller
GEK-106310AB
5.5 CONTROL ELEMENTS
5 SETTINGS
5
Angle:
This setting specifies the size of the blocking region as shown on the Load Encroachment Characteristic diagram
and applies to the positive sequence impedance.
Pickup Delay:
This setting specifies the delay for the trip of Load Encroachment element. After this time expires the signal
Load Encroachment Operate is asserted.
Reset Delay:
This setting specifies the time that the signal Pickup and operate will be asserted after trip conditions have
been removed.
Snapshot events:
The snapshot event setting enables or disables the snapshot event generation for this element.
The Load Encroachment actual values can be viewed at
Actual> Status > Control Elements > Load Encroachment
Table 5–98: LOAD ENCROACHMENT STATUS
The block signals for the frequency rate of change element can be viewed at:
Actual> Status > Protection > Protection
Blocks
:
Table 5–99: LOAD ENCROACHMENT BLOCKS
There are three load encroachment type of signals:
Load Encroachment Block:
Writing status. When this signal is asserted the Load Encroachment function is blocked until
this signal is eliminated and the positive sequence voltage is above the settable level programmed in the Min. Voltage
setting.
Load Encroachment pickup:
Reading state. This state is asserted when the conditions for the operate are fulfilled.
Load Encroachment operate:
Reading state. This state is asserted after the conditions for the operate are fulfilled at least
during the period of time programmed in the pickup delay setting.
LOAD ENCROACHMENT STATUS
LOAD ENCR1 PKP
LOAD ENCR1 OP
LOAD ENCR2 PKP
LOAD ENCR2 OP
LOAD ENCR3 PKP
LOAD ENCR3 OP
LOAD ENCROACHMENT BLOCKS
LOAD ENCR1 BLOCK
LOAD ENCR2 BLOCK
LOAD ENCR3 BLOCK
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...