4-20
F650 Digital Bay Controller
GEK-106310AB
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
4
4.1.8.5 INPUT/OUTPUTS
Section that contains the settings for all input and output boards and the Force Outputs and Virtual inputs activation tools.
Table 4.12: GENERAL OVERVIEW OF "INPUTS/OUTPUTS" SETTINGS MENU.
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
This section shows the settings related to inputs and outputs for the different boards available in F650 (F, G, H, J).
Table 4.13: GENERAL OVERVIEW OF "INPUTS/OUTPUTS>CONTACT I/O" SETTINGS MENU.
4.1.8.6 RELAY CONFIGURATION
This is the relay configuration section in which the relay can be configured using internal states or already compiled
equation on PLC Editor.
Table 4.14: GENERAL OVERVIEW OF RELAY CONFIGURATION MENU:
Frequency rate of
change
Frequency rate of change function (81R).Grouped element.
Load Encroachment
Load Encroachment function. Grouped element.
INPUTS/
OUTPUTS
Contact I/O
Inputs and outputs settings for all boards in F650. The I/O settings
configuration can only be performed through EnerVista 650 Setup, not
HMI available.
Force Outputs (*)
This menu allows activating each contact output in the relay, to facilitate
maintenance testing. On line mode only.
Virtual Inputs (*)
This menu allows operating virtual inputs. These variables are used as
inputs to logic schemes configured in the relay. Virtual inputs can be
operated in a latched mode (32 latched virtual inputs) or in Self-reset
mode (32 self reset virtual inputs).
Remote Comms.
This menu allows configuring remote inputs coming from other devices
through GSSE messages. Available for IEC61850 (6) models only.
CONTACT I/O
Board F
Board located in first slot, always connected.
Board G
Board located in second slot, depends on model definition. If model is
type G0 there is no board in second slot.
Board H
Board located in first slot of CIO Module (external inputs/outputs module)
Board J
Board located in second slot of CIO Module (external inputs/outputs
module)
RELAY CONFIG
Outputs
Configuration of contact output operate and reset signals for all boards.
LEDs
15 LEDs fully configurable from any logical variable, contact or virtual
input. First 5
LEDs are latched by hardware, the rest are self-reset but
can be latched through PLC configuration. From the LED configuration
screen, it is possible to print the vertical LED label for the relay.
Operations
Configurable operations up to 24. Operation texts, interlocks, final states,
frontal keys, time outs and masters.
Protection Elements
This tab allows assigning operands (logic signals) as inputs to different
protection elements. To block, reset, initiate the different protection
elements inputs.
Oscillography
Trigger and up to 16 digital channels to be included in oscillography
records, are programmable from any logical variable, contact or virtual
input. Text configuration is only for off-line mode.
NOTE:
This screen is used for the configuration of digital channels and
oscillography trigger. The rest of parameters, such as function enabling/
disabling, sampling rate, number of oscillography files, etc. must be set
on the
Setpoint>Product Setup>Oscillography
menu.
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...