GEK-106310AB
F650 Digital Bay Controller
5-123
5 SETTINGS
5.6 INPUTS/OUTPUTS
5
5.6.4.2 OUTPUT STATUS SIGNALS
Boards types 1 and 2 have both 8 outputs, so the representation is the same for both types as shown in Table 5–103:
Actual > Inputs/Outputs >Contact Output Status
Real status of the contact output, which corresponds to the transformation of the output activation signal (Contact output
operate), by the logic applied to this output in “
Setpoint > Inputs/Outputs >Contact I/O > Board X
”
Actual > Inputs/Outputs > Contact Output Operates
Activated or deactivated status of those variables used internally to operate a contact output.
Actual > Inputs/Outputs > Contact Output Resets
These are the logic signals associated to the contact output reset, which produce the reset of those signals previously
configured as Latched. Configuration for the contact output reset signal is set at
Setpoint > Relay Configuration >
Outputs > Contact Output Reset
.
Actual > Inputs/Outputs >I/O Board Status
These signals are associated to the different I/O boards. There are internal signals that provide information about the status
of these boards, indicating whether there is any anomaly in the board, or whether the board is not available in the relay
according to the relay model.
Table 5–103: CONTACT OUTPUT SIGNALS
Being X the corresponding board in each case
CONTACT OUTPUT STATUS
CONTACT OUTPUT OPERATES
CONTACT OUTPUT RESETS
IO BOARD STATUS
CONT OP_X_01
CONT OP OPER_X_01
CONT OP RESET_X_01
BOARD F STATUS
CONT OP_X_02
CONT OP OPER_X_02
CONT OP RESET_X_02
BOARD G STATUS
CONT OP_X_03
CONT OP OPER_X_03
CONT OP RESET_X_03
BOARD H STATUS
CONT OP_X_04
CONT OP OPER_X_04
CONT OP RESET_X_04
BOARD J STATUS
CONT OP_X_05
CONT OP OPER_X_05
CONT OP RESET_X_05
CONT OP_X_06
CONT OP OPER_X_06
CONT OP RESET_X_06
CONT OP_X_07
CONT OP OPER_X_07
CONT OP RESET_X_07
CONT OP_X_08
CONT OP OPER_X_08
CONT OP RESET_X_08
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...