GEK-106310AB
F650 Digital Bay Controller
5-103
5 SETTINGS
5.5 CONTROL ELEMENTS
5
5.5.5.6 LOGIC FOR BLOCKING PROTECTION FUNCTIONS DURING THE RECLOSING CYCLE
The F650 autoreclose generates a series of internal signals that allow performing block logics for Protection elements
during the reclosing cycle. These signals are blocks after autoreclose shots (
BLK AFTER SHOT
). For example, if the user
wants to block a protection element during the complete reclosing cycle, it is necessary to configure a signal as an OR of
the four blocking signals provided after each reclosing cycle in the logic configuration tool
Setpoint > Logic Configuration
,
and then use it to block the desired protection elements at
Setpoint > Relay Configuration > Protection Elements
.
Figure 5–27:shows an example of the logic configuration for the block signal during the reclosing cycle.
Figure 5–27: BLOCK SIGNAL DURING THE RECLOSING CYCLE
Figure 5–28: shows an example of the autoreclose initiation and protection element block signals after the different trips.
The autoreclose initiate signal is configured to the relay general trip that corresponds to virtual output 83 configured in the
logic configuration tool, and a physical contact to generate an external autoreclose initiation.
In the example shown on the figure, the 50PH element block signal is configured as a combination of block by digital input,
block by non-trip permission of the directional element, and finally the element will remain blocked during the reclosing
cycle. This means that only the first trip can be executed by the phase instantaneous overcurrent element; after the first
reclose trip, the element will remain blocked until the end of the cycle.
Figure 5–28: CONFIGURATION EXAMPLE OF THE RECLOSE INITIATION AND BLOCK SIGNALS
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...