GEK-106310AB
F650 Digital Bay Controller
B-7
APPENDIX B
B.3 DATA TYPE
B
B.3DATA TYPE
TYPE LENGTH
DESCRIPTIÓN
F1
1
Boolean data type.
As it is a bit, for evaluating it we need a memory address and a bit. For example: Value
0x1A41-0001101001000001b
Bit 15 0
Bit 14 0
Bit 13 0
Bit 12 1
Bit 11 1
Bit 10 0
Bit 09 1
Bit 08 0
Bit 07 0
Bit 06 1
Bit 05 0
Bit 04 0
Bit 03 0
Bit 02 0
Bit 01 0
Bit 00 1
F2
2
Integer with 4 bytes sign.
It has to be scaled, by multiplying by 1000 the value to be sent, or dividing between 1000 the received value. For
example, if a value of 34509 is received, the converted value will be 34,509, and for writing value 334, we must send
334.000.
This prevents the loss of accuracy involved in using float values.
Example: 12312d=0x00003018.
Real Value = 12312/1000=12,312
F3
2
4-byte Floating
Example: 1240.5560x449B11CB
F4
1
Integer with 2 bytes sign.
Example: 1230x007B
F5
2
Integer without 4 bytes sign.
Example: 123120x00003018
F6
4
8 bytes Float
Example: 123.3240x405ED4BC6A7EF9DB
F7
1
Characters without sign. As it needs to be sent in a register, i.e. in two bytes, the character will go below.
Example: ‘
β
’x00E1
F8
1
Characters with sign As it needs to be sent in a register, i.e. in two bytes, the character will go below.
Example: ‘A’x0041
F9
16
String. Chain of characters with a fixed length (32 bytes). The end of the string is marked with a “\0”.
Example: “ABC”0x41x42x43x00....
F10
1
This is a 16-bit integer without sign. Each value that can be taken by this integer will have a correspondence in the
database Auxiliary Table. In this table we can find the corresponding chain, which must be shown for each value. In
the memory, only an integer value will be received.
Example: 0, 1Correspond to CLOSE, OPEN
F11
3
Milliseconds passed since 1/1/2000 at 00:00:00.000.
F12
1
Unsigned int 16 bit (enumerated), example: Value Ox0EBE is the FAULT TYPE 0=GROUND
1=PHASE
2=3 PH
3=AG
4=ABG
5=AB
6=BG
7=BCG
8=BC
9=CG
10=CAG
11=CA
12=NAF
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...