F650 Digital Bay Controller
GEK-106310AB
13.1 SYMPTOMS AND RECOMMENDED ACTIONS
13 F650 TROUBLESHOOTING GUIDE
13
CATEGORY
SYMPTOM
POSSIBLE CAUSE
RECOMMENDED ACTION
Communications
Cannot see properly
the web server in F650
with Windows XP.
Some windows are in
grey with a red cross
mark.
1.- Disabled Java options in Advanced
Internet Explorer properties or high
level of security
2.- Nor Java Virtual Machine installed.
1.1- Go to Advanced in Internet
options
for Internet explorer and select the
three selections in Microsoft VM (Java
Virtual Machine) and deselect any
other virtual machine not Microsoft, for
example SUN.
In case Microsoft VM is not installed in
the computer, the user must install it
using the Microsoft VM installation
program msjavx86.exe
For internet explorer 6.0 or higher it is
not included by default.
1.2.- Try to set a lower level of security
in
internet explorer options.
1.3.-Delete temporary internet files in
"General" screen in internet explorer
options.
Communication Enervista 650 Setup
does not retrieve osc,
fault reports and Data
Logger files
Bad communication in TFTP using
Windows 2000
Disable and Enable the Ethernet
connection on Control Panel inside
Windows 2000. Try again
2.1- Install either Microsoft or Sun Java
Virtual Machine
Communication
Enervista 650 Setup
does not retrieve osc,
fault reports and Data
Logger files
Bad communication in TFTP using
Windows 2000
Disable and Enable the Ethernet
connection on Control Panel inside
Windows 2000. Try again to retrieve
files from relay
Firmware and bootware upgrade
Bootware
The relay gets stuck
during the upgrading
process after switching
off and on the relay,
giving the following
error message:
“ERROR Setting relay
in configuration mode.
Retry?
- The relay does not communicate via
the front RS232 port
To perform the bootware upgrading
process it is necessary to connect the
unit thought the front RS232 port.
check:
•
Serial cable correct(straightthrouhg)
and undamaged.
•
Settings selection in Enervista 650
Setup Communication>Computer
Settings”:
o
Com port selected must be the
one that is being used to perform
this procedure
o
Parity set to NONE
o
Baudrate set to 19200
o
Control type: No control type
o
Modbus slave number: any
Note: if the bootware upgrading
procedure got stuck at this point
the relay will not be upgraded. After
switching it off and on will continue
working with the former firmware
and bootware versions
.
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...