A-30
F650 Digital Bay Controller
GEK-106310AB
A.1 LOGIC OPERANDS
APPENDIX A
A
OPERANDS - F650 - MODEL FX - GX
INTERNAL SYSTEM STATUS (CONT.)
Synchrocheck
Synchrocheck BLK INP
Synchronism element block
Synchrocheck OP
Synchronsim condition (Dv, Dj and Df are within the set
range)
SYNCHK CLOSE PERM
Closing permission for the synchronism element:
(SYNCHK OP) OR (SYNCHK CON OP)
Synchrocheck COND
OP
Active if when it is set, any of the three following
conditions is met:
DL-DB OPERATION
Dead line – dead bus condition
DL-LB OPERATION
Dead line – live bus condition
LL-DB OPERATION
Live line – dead bus condition
SLIP CONDITION
Slip conditions are met
BUS FREQ > LINE
FREQ
Bus Frequency higher than line frequency
BUS FREQ < LINE
FREQ
Bus Frequency lower than line frequency
Autorecloser
AR LEVEL BLOCK
Recloser element block by level
AR PULSE BLOCK
Recloser element block by pulse
AR PULSE UNBLOCK
Recloser element unblock by pulse
AR INITIATE
Reclose initiate
AR CONDS INPUT
Reclose permission condition in input to Function 1 =
there are conditions
AR CLOSE BREAKER
Closing permission for the recloser
AR OUT OF SERVICE
Recloser out of service
AR READY
Recloser READY
AR LOCKOUT
Recloser in LOCKOUT
AR BLOCK
Recloser BLOCKed
AR RCL IN PROGRESS Recloser – Cycle in progress
AR LCK BY ANOMALY
Recloser – LOCKOUT by anomaly (reclosing command
during cycle in progress)
AR LCK BY FAIL OPEN
Recloser – LOCKOUT by failure to open
AR LCK BY FAIL CLOSE Recloser – LOCKOUT by failure to close
AR LCK BY USER
Recloser – LOCKOUT by external operation (e.g.:
manual opening with cycle in progress)
AR LCK BY CONDS
Recloser – LOCKOUT by lack of reclosing conditions
AR LCK BY TRIPS
Recloser – LOCKOUT by number of trips
AR LCK BY SHOTS
Recloser – LOCKOUT by number of shots
AR BLK AFTER 1 SHOT Recloser – Block after first shot
AR BLK AFTER 2 SHOT Recloser – Block after second shot
AR BLK AFTER 3 SHOT Recloser – Block after third shot
AR BLK AFTER 4 SHOT Recloser – Block after fourth shot
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...