6 ACTUAL VALUES
6.2 STATUS
6
6.2.12.7 BREAKER MAINTENANCE
Actual> Status > Records Status > Breaker Maintenance
This screen shows the breaker status related to breaker maintenance. Other statuses are provided in the different
switchgear or breaker status signals.
Table 6–36: BREAKER MAINTENANCE STATUS
The breaker maintenance inputs are signals that can be configured at Setpoint > Relay Configuration > Protection
Elements:
RESET KI2t COUNTERS
Signal to reset and set to zero all the KI2t counters (for all phases)
RESET BKR COUNTERS
Signal to reset and set to zero all the breaker counters (number of openings and closings
and alarms)
KI2t PHASE A ALARM
Alarm signal for maximum breaking capacity in phase A exceeded
KI2t PHASE B ALARM
Alarm signal for maximum breaking capacity in phase B exceeded
KI2t PHASE C ALARM
Alarm signal for maximum breaking capacity in phase C exceeded
BKR OPENINGS ALARM
Alarm related to the maximum number of breaker openings
BKR OPEN 1 HOUR ALARM
Alarm related to the maximum number of breaker openings in one hour
BREAKER OPENINGS
Counter of the total number of openings performed by the breaker
BREAKER CLOSINGS
Counter of the total number of closings performed by the breaker
KI2t PHASE A
kI
2
t phase A counter (total accumulative breaking level – phase A)
KI2t PHASE B
kI
2
t phase B counter (total accumulative breaking level – phase B)
KI2t PHASE C
kI
2
t phase C counter (total accumulative breaking level – phase C)
BKR OPENING TIME
Time to set a failure in opening the breaker.
BKR CLOSING TIME
Time to set a failure in closing the breaker.
BKR OPEN TIMING
Exact time in opening the breaker
BKR CLOSE TIMING
Exact time in closing the breaker
Breaker opening and closing time signals are configured at
Setpoint > Relay Configuration > Switchgear
for the related
switchgear device.
BREAKER MAINTENANCE INPUTS
RESET KI2t COUNTERS
RESET BKR COUNTERS
BREAKER MAINTENANCE STATUS
KI2t PHASE A ALARM
KI2t PHASE B ALARM
KI2t PHASE C ALARM
BKR OPENINGS ALARM
BKR OPEN 1 HOUR ALARM
BREAKER OPENINGS
BREAKER CLOSINGS
KI2t PHASE A
KI2t PHASE B
KI2t PHASE C
BKR OPENING TIME
BKR CLOSING TIME
BKR OPEN TIMING
BKR CLOSE TIMING
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...