GEK-106310AB
F650 Digital Bay Controller
7-33
7 IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR F650
7
2.2.5.2 AuxPTUV
This logical node class is used for auxiliary undervoltage and has 3 instances inside the device.
Notes:
TmVCrv object uses Enum type setCharact_2 (See the Enum types implementation section).
ACT includes origin attribute in ST, this is implemented according to Tissue 68.
2.2.6 PTUF (UnderFrequency)
This logical node class is used for phase underfrequency and has 3 instances inside the device.
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
PTUV class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
PTUV
Undervoltage
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Status Information
Str
ACD
Start
M
TUV PKP
Op
ACT
Operate
M
TUV OP
Blk
ACT
Block
E
TUV BLK
Settings
TmVCrv
CURVE_2
Operating curve type
O
Curve ( definitive, inverse )
StrVal
ASG
Start value
O
Pickup Level (3 – 300)
TmMult
ASG
Time dial multiplier
O
Delay (0 – 900)
PTUVEna
SPG
Function TUV enable
E
Function
PTUF class
Attribute
Name
Attribute
Type
Explanation
M/O/E
Notes
PTUF
OverFrequency
Data
Common Logical Node Information
Mod
INC
Mode
M
Status-only
Beh
INS
Behaviour
M
Health
INS
Health
M
NamPlt
LPL
Name plate
M
Status Information
Str
ACD
Start
M
TUF PKP
Op
ACD
Operate
M
TUF OP
Blk
ACT
Block
E
TUF BLK
Settings
StrVal
ASG
Start value (frequency)
O
Pickup Level (20-65)
BlkVal
ASG
Voltage Block Value
O
Minimun Voltage (10-300)
OpDlTmms
ING
Operate Delay Time
O
Trip Delay (0-900000)
Units in miliseconds
RsDlTmms
ING
Reset Delay Time
O
Reset Delay (0-900000)
Units in miliseconds
PTUFEna
SPG
Function TUF enable
E
Function (Enable,Disable)
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...