Proservo NMS5
56
Hauser
7.1.7
Analogue Output (GVH250 to 256)
When specified and ordered from Hauser, NMS5 is equipped with analogue output hardware
installed. Function settings may be changed as follows:
7.1.8
Contact Relay Alarm Output (GVH240 to 247)
When specified and ordered from Hauser, NMS5 is equipped with contact relay alarm output hard-
ware installed. Function settings may be changed as follows:
Function
Setting
Assign Output 1
Assign level or temperature to channel 1 output.
Adjust 4mA
Set desired value at which level or temperature outputs 4 mA.
Adjust 20mA
Set desired value at which level or temperature outputs 20 mA
Assign Output 2
Assign level or temperature to channel 2 output.
Adjust 4mA
Set desired value at which level or temperature outputs 4 mA
Adjust 20mA
Set desired value at which level or temperature outputs 20 mA.
Device at Alarm
Select type of output for alarm
Function
Setting
Select Relay
Select relay number from 1, 2, 3 or 4.
Assign Relay
Select output definition from range of choices: None, Level, Liquid
Temperature, Caution, Warning, Emergency Error, Balance Signal.
Relay Function
Select High or Low.
Switching Point
Set value at which relay is activated.
Hysteresis
Set hysteresis value for selected relay.
Relay on Alarm
Select relay of Normal Open or Normal Closed.
On Delay Time
Set time delay value for alarm output start.
Off Delay Time
Set delay value for alarm output stop.
7 Commissioning