Proservo NMS5
Hauser
73
G8V4H6 LIQ. WAIT TIME
G8V4H7 OPE. WAIT TIME
Item
Procedure
Remarks
Figure. 73:
G8V4H6
1.
Select G8V4H6 "LIQ.
WAIT TIME" to
determine the displacer
weight calibration
interval between each
measuring point in the
liquid.
•
Set access code to 51. A
small turbulence made by
the movement of displacer
itself may cause the liquid
surrounding displacer to be
unstable for the accurate
measurement.
2.
Enter desired waiting
time by pr or -
key, and select E to
enter.
•
This function allows
displacer to hold in each
calculated position before
actual measurement is
proceeded based on the
entered value.
Item
Procedure
Remarks
Figure. 74:
G8V4H7
1.
Select G8V4H7 "OPE.
WAIT TIME" to
determine the operation
holding time limit to
accept "BAL. LEVEL"
before the actual
operation starts.
•
Set access code to 51.
Entire operation begins
only when the condition
described in "BAL. LEVEL"
is achieved.
2.
Enter desired waiting
time by pr or -
key, and select E to
enter.
•
This function determines
how long for the NMS to
wait if "BAL. LEVEL" can
not be established before
quitting entire operation.
TANK
PROFILE
Function
Group
LIQ. WAIT
TIME
GVH=846
Matrix Group : TANK PROFILE
TANK
PROFILE
Function
Group
OPE. WAIT
TIME
GVH=847
Matrix Group : TANK PROFILE
7 Commissioning