Proservo NMS5
Hauser
51
6.5
Operation of Displacer
The operation of the displacer for level, bottom level, interface level, and density measurement is possible by
touch control.
Item
Procedure
Remarks
Figure. 53:
Static Matrix
Figure. 54:
Touch Control
1.
Select function
groupGVH=020
OPERATION
2.
Select item
OPERATION. The
LCD shows the
command given to
NMS5and the
displacer position.
•
Set access code to 50.
•
If editing has previously
been enabled by a valid
access code, then the
request for the code will
not appear.
Figure. 55:
Operation of Displacer
3.
The following
commands are
available at this
position:
LEVEL
UP
STOP
BOTTOM LEVEL
UPPER INTERF. LEV*
MIDD.INTERF.LEV*
UPPER DENSITY*
MIDDLE DENSITY*
DENSITY BOTTOM*
WATER DIP*
REPEATABILITY TEST
•
Interface and density
measurements are not
available unless
specifically requested.
•
Density profile
measurement is
explained in section "7
Commissioning".
•
The optional operation
commands are available
when such options are
set.
OPERATION
OPERATION
Level
Bottom
Level
Upper Interface
Level
Middle Interface
Level
Density Bottom
Water
Dip
Middle Density
Upper Density
6 Operation