Proservo NMS5
Hauser
101
11.5
Initial Weight Calibration
11.5.1
Displacer Weight Calibration
Weight table calibration must be done after completing hall sensor adjustment. The calibration procedures will
vary depending on the measurement specifications. Use this procedure ONLY for NMS5 with level measure-
ment function.
Note!
Wind and vibration may affect weight table calibration.
It is not necessary to do initial calibration for Startup "All-in-one" (displacer attached) shipments.
Weight Calibration for Standard Specification
Item
Procedure
Remarks
Figure. 96:
Calibration 1-A
1. Enter Access Code 51.
2. Confirm the following
data.
G3V4H0 wire Drum
Circum (engraved on
wire drum)
G3V4H1 Wire Weight
Standard SUS = 1.40
PFA=4.55
Hastelloy=2.8
G3V4H2 Displacer
Weight (engraved on
displacer)
Figure. 97:
Calibration 2-A
3. Displacer is located in
the calibration window
or the maintenance
chamber. Set the dis-
placer in the following
order.
Set Operation = STOP
Set G3V7H9=0.0
Set G3V7H3=ON
at "Displacer Down? +/
-"
Enter No "-" for calibra-
tion window and enter
yes "+" for maintenance
chamber.
Figure. 98:
Calibration 3-A
4. Leave the displacer
until Sa and Sb are sta-
ble. Press "E" and "-"
keys at the same time.
5. Return the displacer to
the original position.
e.g.
300.110
e.g.
250.2 g
H
V
0
1
2
4
xxx.xxx
x.xx
xxx.x
Service
Matrix: G3
Wire Drum
Displacer
51
ACCESS CODE
e.g.
+
-
STOP
OPERATION
ON
WEIGHT CALIB.
Displacer down?
-
E
2xxxx 1xxxx
0.0 Low on: E& -
11 Displacer and Measuring Wire