Matrix group
Function group
Item
Access
code
Short description
Default value
Set
Select
Display
Possible settings,
selection, or display
Index No,
GVH
MEAS. WIRE & DRUM
WIRE DRUM CIRC.
340
342
341
51
51
51
SERVICE
DISPLACER VOLUME
VOLUME TOLERANCE
344
WIRE WEIGHT
Set
DISPLACER WEIGHT
51
51
51
Set
343
Set
Set
Set
DELAY
DRUM CORRECTION
DISPL. HUNT. COUNT
51
20 x 100 mS
Set
Set
0 - 999.9
0 - 999.9
0 - 999.9
0 - 999.9
0 - 99.9
0 - 999.9
Circumference of wire drum is measured at factory and inscribed
on the wire drum. Used by CPU to calculate Measured Level
Weight of measuring wire per 10 meters. Used by CPU to
determine balance weight. Standard measuring wire is
1.40 g/10 m. PFA wire is 4.55 g/10 m. Hastelloy C wire is
2.8 g/10 m
Weight of displacer is measured at factory and inscribed on
the wire drum. Used by CPU to calculate Measured and Interface
Levels and densities.
Total volume of displacer is measured at factory and inscribed on
the wire drum. Used by CPU to calculate Interface Levels and
Densities.
BALANCE VOLUME
51
Balance volume of displacer is measured at factory and inscribed
on the wire drum, approximately one-half of Displacer
Volume (G3V4H3). Used by CPU to calculate Measured and
Interface Levels.
Displacer immunity to variation in liquid surface level during
Balance condition. Based on density = 1.0, setting for standard
50 mm displacer is 1.0 mL (1 g). Increase to counter turbulence
and waves. Level accuracy varies inversely as Volume Tolerance.
Interval until displacer responds to change in liquid level. Increase
to counter small
Used only for SW V2.xx
51
$ElNESTHENUMBEROFTIMESDISPLACERSERCHESFORBALANCE
condition.To balance on solid surface set = non-zero (e.g. 1)
300.00 mm
1.40 g/10 m
255.0 g
145.0 mL
60 mL
1.0 mL
0.00 mm/m
0 count
Set
Set
0 - 99 x 100mS
0 - 99
0 - 99.00
345
347
348
349
13 Matrix