Proservo NMS5
Hauser
65
7.5.5
Analog Output
Setting of analog output 4-20mA is available when ordered from Hauser. NMS5 is delivered with ana-
log output hardware installed. For the following matrix parameter settings, Access code 51, is required.
Note!
If "LEVEL", confirm GVH158 (Prosafety) is "NO".
Matrix
Item
Setting
G2V5H0
Assign Output
Assign analog output (Level or Temperature) for channel 1.
G2V5H1
Adjust 4mA
Set level or temperature value for 4mA output on channel 1.
Available only when G2V5H0= "Level" or "Liquid Temp"
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
G2V5H2
Adjust 20mA
Set level or temperature value for 20mA output on channel 1. Avail-
able only when G2V5H0 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
G2V5H3
Assign Output 2
Assign analog output (Level or Temperature) for channel 2.
G2V5H4
Adjust 4mA
Set level or temperature value for 4mA output on channel 2.
Available only when G2V5H3 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0
°C
G2V5H5
Adjust 20mA
Set level or temperature value for 20mA output on channel 2.
Available only when G2V5H3 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0
°C
G2V5H6
Device at Alarm
Select type of output for alarm. Select from OFF, HOLD current
output, Maximum value or Minimum value.
Default : OFF
7 Commissioning