6.14.9 Defining Send Clock and Update Time
6.14.9.1 Configuring the Send Clock Time
Procedure
1. Open the
HW Config
tool.
2. Select the station with the PROFINET
®
devices to be involved in IRT communication, for example PNxIO.
3. Select the menu [Edit
→
PROFINET IO
→
Domain management].
4. In the next window, open the
Sync Domain
tab and in the
Send clock time [ms]
field, select an appropriate time for the process, for
example 1.000 ms, then click on
OK
.
e3
0b
h5
30
.1
0
Illustration 94: Configuring a Send Clock for PROFINET
®
IRT
Commissioning
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
126 | Danfoss A/S © 2019.10