Troubleshooting by Indication on the Remote Controller
252
Note:
∗
1. Check the low pressure value by using pressure
gauge in operation.
∗
2. Compare the actual measurement value by pressure
sensor with the value by the pressure gauge.
(To gain actual measurement value by pressure
sensor, measure the voltage at the connector
[between (2)-(3)] and then convert the value into
pressure .)
∗
3. Compare the thermistor resistance value with the
value on the surface thermometer.
Refer to P.348.
Refer to P.351.
Refer to P.372.
CHECK 12
CHECK 2
CHECK 3
CHECK 12