Troubleshooting by Indication on the Remote Controller
288
B
NO
Disconnect
the outdoor -
outdoor unit
transmission wiring, and
then check with a
single system
whether or not
it is normal.
Replace the
outdoor unit
PCB.
NO
YES
Operation
ready lamp (H2P) is
blinking.
YES
NO
Lamp
does not go
OFF for 12 minutes or
more.
Press and hold
the RESET
button on the
outdoor unit PCB
for 5 seconds.
NO
YES
Is
indoor -
outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Fix the indoor -
outdoor or
outdoor - outdoor
unit transmission
wiring.
Mount the DIII-
NET expander
adaptor.
YES