Troubleshooting by Indication on the Remote Controller
79
Troubleshooting
Refer to P.369.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Is the thermistor
normal?
Normal (The
error is caused
by defective
contact.)
YES
NO
Replace the
indoor unit PCB.
YES
Replace the
thermistor.
NO
5 k
Ω
to 90 k
Ω
CHECK 11
Remove the thermistor
from the indoor unit PCB,
and then insert it again.
Remove the thermistor
from the indoor unit PCB,
and then make resistance
measurement of the
thermistor using a multiple
meter.
CHECK 11