Troubleshooting by Indication on the Remote Controller
271
NO
YES
Is
220 ~ 240 V
of power reaching
the magnetic contact
switch coil?
Replace the
magnetic contact
switch.
NO
YES
Is 220 ~
240 V at the
connector inverter
PCB.
Is
220 ~ 240 V
at the connector
outside PCB side?
Replace the
inverter PCB.
NO
YES
Does
the voltage
between
terminals P2 (or P3)
and N3 gradually rise to
556 VDC (Y1, YL) or
283 VDC (TL)
after turning
ON?
Replace the
inverter PCB.
YES
NO
Replace the
outside unit PCB.
Check the
transmission
wiring between
the outside unit
PCB and inverter
unit.
A