Troubleshooting by Indication on the Remote Controller
286
Troubleshooting
YES
NO
NO
A
B
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Has
the indoor
or outdoor unit
PCB been
replaced, or has the
indoor - outdoor or
outdoor - outdoor
unit transmission
wiring been
modified?
All indoor
unit remote
controllers of the same
refrigerant system
display "
U4
".
YES
Press and hold
the RESET
button on the
outdoor unit main
PCB for 5
seconds.
∗
The unit will not
operate for up
to 12 minutes.
Fix the indoor-
outdoor or
outdoor-outdoor
unit transmission
wiring.
NO
YES
Replace the
indoor unit PCB
indicated by the
error code "
U4
".
YES
Is indoor -
outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Outdoor
unit PCB micro-
computer monitor
(HAP) blinks.
NO
NO
Supply 220~240 V.
YES
The
voltage between
terminals L1 and N of
the outdoor unit PCB
is 220~240 V.
Reset the power supply.