Troubleshooting by Indication on the Remote Controller
81
Troubleshooting
Refer to P.369.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Normal (The
error is caused
by defective
contact.)
YES
NO
Replace the
indoor unit PCB.
YES
Replace the
thermistor.
NO
Remove the thermistor
from the indoor unit PCB,
and then insert it again.
Is the thermistor
normal?
Remove the thermistor
from the indoor unit PCB,
and then make resistance
measurement of the
thermistor using a multiple
meter.
5 k
Ω
to 90 k
Ω
CHECK 11
CHECK 11