Troubleshooting by Indication on the Remote Controller
358
Note:
∗
1. “Superheating temperature control” in cooling is
conducted by indoor unit electronic expansion valve.
∗
2. Superheating temperature control in heating is
conducted by outdoor unit electronic expansion valve
(EVM).
∗
3. Guideline of superheated degree to judge as wet
operation
1
Suction gas superheated degree: Not more than
3°C;
2
Discharge gas superheated degree: Not
more than 15°C, except immediately after
compressor starts up or is running under drooping
control.
(Use the above values as a guide. Depending on the
other conditions, the unit may be normal despite the
values within the above range.)
Degraded
evaporating
capacity
Dirty evaporator
←
Does the heat exchanger
get clogged?
Decreased
airflow
rate
Decreased
fan output
Defective
fan motor
Defective
service
monitor
PCB
(including
capacity
setting)
←
Can the fan motor
be rotated with
hands?
Are the motor coil
resistance and
insulation normal?
High
airflow
passage
resistance
Dirty filter
Obstacles
←
Is the air filter
clogged?
←
Is there any
obstacle in the
airflow passage?
A