Troubleshooting by Indication on the Remote Controller
87
Troubleshooting
Refer to P.369.
Connector is
connected to the
indoor unit PCB.
Resistance
is normal when
measured after
disconnecting the
thermistor from the indoor
unit PCB. (7.2k
Ω
~
112k
Ω
)
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Replace the
indoor unit PCB.
Connect the
thermistor and
turn ON again.
NO
NO
Replace the
thermistor.
YES
CHECK 11
YES
CHECK 11