Troubleshooting by Indication on the Remote Controller
158
Troubleshooting
The alarm indicator is displayed when the fan only is
being used also.
Refer to P.369.
Connector is
connected to outdoor
unit PCB.
NO
YES
Connect the
connector and
turn ON again.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit PCB.
NO
Replace the
thermistor.
CHECK 11
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
Replace the
outdoor unit
PCB.
CHECK 11