Troubleshooting by Indication on the Remote Controller
140
Troubleshooting
Note:
∗
1. Compare the resistance values of the discharge pipe
thermistor with measurements of a surface
thermometer.
(For temperature and resistance characteristics of a
thermistor, refer to P.371.)
∗
2. Compare the discharge pipe temperature checked
by the Service
Checker with the resistance of the thermistor (refer to
∗
1).
Refer to P.351.
NO
YES
YES
Replace the
discharge pipe
thermistor.
Are
discharge
pipe thermistor
characteristics
normal?
(
∗
1)
NO
Replace the main
PCB.
Is PCB
detection temperature
normal?
(
∗
2)
· The discharge pipe thermistor is normal and the
main PCB temperature detection is also normal.
· In fact, discharge pipe temperature is rising.
CHECK 3
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Connect the Service
Checker.
Restart operation after
resetting operation.
CHECK 3