Troubleshooting by Indication on the Remote Controller
50
Troubleshooting
NO
YES
YES
YES
The
float switch
is connected to
connector of the
indoor unit
PCB.
The float
switch functions
normally.
The
drain
pump is
connected to
connector terminals
of the indoor
unit PCB.
NO
NO
Replace the float
switch.
Modify the float
switch's
connection and
turn ON again.
Connect the
drain pump and
turn ON again.
Is power
supply 220~240V
provided?
Water builds
up in the drain
pan.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
YES
NO
YES
NO
Provide
220~240V power
supply.
NO
A
short circuit
connector is
connected to
PCB.
YES
Becomes
normal when
connector of the indoor
unit PCB is short
circuited
NO
The
float
switch contact
is forming a short
circuit (continuity check
with connector
disconnected)
Connect either a
short circuit
connector or float
switch and turn
ON again.
NO
Defective indoor
unit PCB.
Loose the
connection of
connector.
YES
A