Troubleshooting by Indication on the Remote Controller
126
Troubleshooting
Refer to P.378.
Refer to P.379.
YES
NO
Connector of
fan motor is
disconnected.
Is the pulse
inputted?
NO
YES
Connect the
connector.
Replace the fan
motor of outdoor
unit.
Replace the
outdoor unit
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Check on connector of
fan motor (Power
supply cable)
Check on pulse input of
position signal of fan
inverter PCB
YES
NO
Is there
any obstacle
around the fan?
Remove the
obstacle.
NO
YES
Can the
fan be turned
smoothly with
hand after disconnect
the connector of
fan motor?
Replace the fan
motor of outdoor
unit.
CHECK 16
CHECK 17
CHECK 16
CHECK 17