![Daikin VRVII Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/daikin/vrvii/vrvii_manual_4705257064.webp)
Troubleshooting by Indication on the Remote Controller
59
NO
YES
Replace the fan
motor.
Turn ON the power.
Remove the signal
connector from the fan
motor and check the
resistance (
∗
2).
The
resistors
among U, V, and
W are unbalanced or
short-circuited.
YES
NO
Between
V
CC
and GND
terminals, and
between GND and H
W
,
H
V
, or
HU
terminals
are short-
circuited.
Replace the fan
motor.
A
Remove the power wire
connector from the fan
motor and measure the
resistance between U
and V, V and W, and W
and U phases (*1).
NO
YES
The
resistance
between the
power wire terminals
of the fan motor and
motor frame (meal
part) is 1 M
Ω
or below.
Replace the fan
motor.
B
Содержание VRVII
Страница 1: ...Pocket Manual Service Diagnosis Si30 701_A...