Troubleshooting by Indication on the Remote Controller
295
Troubleshooting
YES
Has the
indoor or
outdoor
(outside) unit PCB
been replaced, or has
the indoor - outdoor
(outside) or outdoor
(outside) - outdoor
(outside) unit
transmission
wiring been
modified?
Press and hold
the RESET
button on the
master outdoor
(outside) unit
PCB for 5
seconds.
∗
The unit will not
operate for up
to 12 minutes.
Replace the
indoor unit PCB.
Fix the indoor -
outdoor (outside)
unit transmission
wiring.
NO
YES
YES
NO
NO
All
indoor unit
remote controllers
of the same refrigerant
system display
"
U4
."
Is
indoor -
outdoor (outside)
and outdoor (outside)
-outdoor (outside) unit
transmission wiring
normal?
A
Reset the power supply.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Содержание VRVII
Страница 1: ...Pocket Manual Service Diagnosis Si30 701_A...