Symptom-based Troubleshooting
13
4 The system
does not
operate.
The system stops
and immediately
restarts operation.
If the OPERATION
lamp on the remote
controller turns ON,
the system will be
normal. These
symptoms indicate
that the system is
controlled so as not to
put unreasonable
loads on the system.
Normal operation.
The system will
automatically
start operation
after a lapse of 5
minutes.
Pressing the
TEMP ADJUST
button immediately
resets the system.
The remote
controller displays
"UNDER
CENTRALIZED
CONTROL", which
blinks for a period of
several seconds
when the
OPERATION button
is depressed.
The system is
controlled with
centralized
controller. Blinking
display indicates that
the system cannot
be operated using
the remote
controller.
Operate the
system using the
COOL/HEAT
centralized
remote controller.
The system stops
immediately after
turning ON the
power supply.
The system is in
preparation mode
of micro computer
operation.
Wait for a period
of approximately
1 minute.
5 The system
makes
intermittent
stops.
The remote
controller
displays error
codes "
U4
" and
"
U5
", and the
system stops but
restarts after a
lapse of several
minutes.
The system stops
due to an
interruption in
communication
between units
caused by electrical
noises coming from
equipment other
than air
conditioners.
Remove causes
of electrical
noises.
If these causes
are removed, the
system will
automatically
restart operation.
6 COOL-HEAT
selection is
disabled.
The remote
controller displays
"UNDER
CENTRALIZED
CONTROL".
This remote
controller has no
option to select
cooling operation.
Use a remote
controller with
option to select
cooling operation.
The remote
controller displays
"UNDER
CENTRALIZED
CONTROL", and
the COOL-HEAT
selection remote
controller is
provided.
COOL-HEAT
selection is made
using the COOL-
HEAT selection
remote controller.
Use the COOL-
HEAT selection
remote controller
to select cool or
heat.
Symptom
Supposed Cause Countermeasure