Troubleshooting by Indication on the Remote Controller
178
3.43
J8
Thermistor System
Abnormality
Remote Controller Display
J8
Applicable Models
VRVIII-Q Series
Method of Error Detection
Error is detected according to the temperature detected
by each individual thermistor.
Error Decision Conditions
When thermistor is disconnected or short-circuited during
operation
Supposed Causes
Defective thermistor
Defective connection of connector
Defective outdoor unit PCB (control PCB)
Содержание VRVII
Страница 1: ...Pocket Manual Service Diagnosis Si30 701_A...