Troubleshooting by Indication on the Remote Controller
224
Troubleshooting
YES
The
difference
between high
and low pressure when
starting is above
0.2MPa or
more.
NO
YES
Unsatisfactory
pressure
equalization
Check refrigerant
system.
Disconnect the connection
between the compressor
and inverter. Make the
power transistor check
mode ON by service
mode.
A
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Inverter
output
voltage check
Inverter output
voltage is not
balanced. (Normal if
within ±10V for Y1, YL
power supply and ±5V
for TL power supply)
Must be measured
when frequency
is stable.
NO
Replace the
inverter PCB