Troubleshooting by Indication on the Remote Controller
306
YES
YES
NO
Connect the
power supply
wire for the
external control
adaptor for
outdoor unit to
5V supply line.
Replace the PCB
of the external
control adaptor
for outdoor unit.
Replace the
outdoor unit main
PCB.
Check if
the normal
condition monitor
LED for the external
control adaptor for
outdoor unit
blinks.
NO
NO
YES
Set
the C/H
SELECT of
the external
control adaptor for
outdoor unit to “IND”.
Then check if the
error occurs
again.
Check if
the power
supply wire for the
external control adaptor
for outdoor unit is
connected to 5V
supply line.
A