Troubleshooting by Indication on the Remote Controller
242
Troubleshooting
Refer to P.369.
YES
NO
Is the
resistance of
thermistor
correct?
Replace the
inverter PCB.
(Thermistor can
not be removed
from the inverter
PCB)
NO
Is the resetting
possible?
Replace the
inverter PCB.
YES
After resetting,
restart.
Measure the resistance of
radiation fin thermistor.
CHECK 11
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
CHECK 11